Mojave firmware 1.09 FW valuation- Firmware 1.09 Results

Gonzalez, Sigifredo; Gurule, Nicholas S.

This quick note outlines what we found after our conversion with you and your team. As suggested, we loaded 1547-2003 source requirements document (SRD) and then went back and loaded 1547-2018 SRD. This did result in implementing the new 1547-2018 settings. This short report focuses on the frequency-watt function and shows a couple of screen shots of the parameter settings via the Mojave HMI interface and plots of the results of the inverter with FW function enabled in both default and most aggressive settings response to frequency events. The first screen shot shows the 1547-2018 selected after selecting 1547-2003.

More Details

Mojave firmware 1.09 base-line valuation [Memo]

Gonzalez, Sigifredo

The inverter firmware was upgraded to version 1.09 and an initial assessment was conducted on the inverter using the equipment listed above and the response of the inverter can be seen in the following plots. This work is to base-line the response of the inverter to utility conditions and commands and further work will involve the interoperability aspect of the inverter using SunSpec dashboard to conduct the tests and configure the inverter.

More Details

Performance of a Grid-Forming Inverter under Balanced and Unbalanced Voltage Phase Angle Jump Conditions

Conference Record of the IEEE Photovoltaic Specialists Conference

Darbali-Zamora, Rachid; Gurule, Nicholas S.; Hernandez-Alvidrez, Javier; Gonzalez, Sigifredo; Reno, Matthew J.

Renewable energy has become a viable solution for reducing the harmful effects that fossil fuels have on our environment, prompting utilities to replace traditional synchronous generators (SG) with more inverter-based devices that can provide clean energy. One of the biggest challenges utilities are facing is that by replacing SG, there is a reduction in the systems' mechanical inertia, making them vulnerable to frequency instability. Grid-forming inverters (GFMI) have the ability to create and regulate their own voltage reference in a manner that helps stabilize system frequency. As an emerging technology, there is a need for understanding their dynamic behavior when subjected to abrupt changes. This paper evaluates the performance of a GFMI when subjected to voltage phase jump conditions. Experimental results are presented for the GFMI subjected to both balanced and unbalanced voltage phase jump events in both P/Q and V/f modes.

More Details

RADIANCE Cybersecurity Plan: Generic Version

Mccarty, M.V.; Mix Sr.Mix; Knight, M.R.; Eddy, John P.; Johnson, Jay; Gonzalez, Sigifredo

Under its Grid Modernization Initiative, the U.S. Department of Energy (DOE), in collaboration with energy industry stakeholders developed a multi-year research plan to support modernizing the electric grid. One of the foundational projects for accelerating modernization efforts is information and communications technology interoperability. A key element of this project has been the development of a methodology for engaging ecosystems related to grid integration to create roadmaps that advance the ease of integration of related smart technology. This document is the product of activities undertaken in 2017 through 2019. It provides a Cybersecurity Plan describing the technology to be adopted in the project with details as per the GMLC Call document.

More Details

Grid-forming Inverter Experimental Testing of Fault Current Contributions

Conference Record of the IEEE Photovoltaic Specialists Conference

Gurule, Nicholas S.; Hernandez-Alvidrez, Javier; Reno, Matthew J.; Summers, Adam; Gonzalez, Sigifredo; Flicker, Jack D.

Historically, photovoltaic inverters have been grid-following controlled, but with increasing penetrations of inverter-based generation on the grid, grid-forming inverters (GFMI) are gaining interest. GFMIs can also be used in microgrids that require the ability to interact and operate with the grid (grid-tied), or to operate autonomously (islanded) while supplying their corresponding loads. This approach can substantially improve the response of the grid to severe contingencies such as hurricanes, or to high load demands. During islanded conditions, GFMIs play an important role on dictating the system's voltage and frequency the same way as synchronous generators do in large interconnected systems. For this reason, it is important to understand the behavior of such grid-forming inverters under fault scenarios. This paper focuses on testing different commercially available grid-forming inverters under fault conditions.

More Details

Grid-forming Inverter Experimental Testing of Fault Current Contributions

Conference Record of the IEEE Photovoltaic Specialists Conference

Gurule, Nicholas S.; Hernandez-Alvidrez, Javier; Reno, Matthew J.; Summers, Adam; Gonzalez, Sigifredo; Flicker, Jack D.

Historically, photovoltaic inverters have been grid-following controlled, but with increasing penetrations of inverter-based generation on the grid, grid-forming inverters (GFMI) are gaining interest. GFMIs can also be used in microgrids that require the ability to interact and operate with the grid (grid-tied), or to operate autonomously (islanded) while supplying their corresponding loads. This approach can substantially improve the response of the grid to severe contingencies such as hurricanes, or to high load demands. During islanded conditions, GFMIs play an important role on dictating the system's voltage and frequency the same way as synchronous generators do in large interconnected systems. For this reason, it is important to understand the behavior of such grid-forming inverters under fault scenarios. This paper focuses on testing different commercially available grid-forming inverters under fault conditions.

More Details

Implementation of a Grid Connected Battery-Inverter Fleet Model

Rosewater, David; Gonzalez, Sigifredo

Batteries are designed to store electrical energy. The increasing variation in time value of energy has driven the use of batteries as controllable distributed energy resources (DER). This is enabled though low-cost power electronic inverters that are able to precisely control charge and discharge. This paper describes the software implementation of an open-source battery inverter fleet models in python. The Sandia BatterylnverterFleet class model can be used by scientists, researchers, and engineers to perform simulations of one or more fleets of similar battery-inverter systems connected to the grid. The program tracks the state- of-charge of the simulated batteries and ensures that they stay within their limits while responding to separately generated service requests to charge or discharge. This can be used to analyze control and coordination, placement and sizing, and many other problems associated with the integration of batteries on the power grid. The development of these models along with their python implementation was funded by the Grid Modernization Laboratory Consortium (GMLC) project 1.4.2. Definitions, Standards and Test Procedures for Grid Services from Devices.

More Details

Unintentional Islanding Detection Performance with Mixed DER Types

Gonzalez, Sigifredo; Ellis, Abraham; Ropp, Michael E.; Mouw, Chris A.; Schutz, Dustin D.; Perlenfein, Scott J.

Most inverters for use in distribution-connected distributed energy resource applications (distributed generation and energy storage) are tested and certified to detect and cease to energize unintentional islands on the electric grid. The requirements for the performance of islanding detection methods are specified in IEEE 1547-2018, and specified conditions for certification- type testing of islanding detection are defined in IEEE 1547.1. Such certification-type testing is designed to ensure a minimum level of confidence that these inverters will not island in field applications. However, individual inverter certification tests do not address interactions between dissimilar inverters or between inverter and synchronous machines that may occur in the field. This work investigates the performance of different inverter island detection methods for these two circumstances that are not addressed by the type testing: 1) combinations of different inverters using different types of islanding detection methods, and 2) combinations of inverters and synchronous generators. The analysis took into consideration voltage and frequency ride- through requirements as specified in IEEE 1547-2018, but did not consider grid support functionality such as voltage or frequency response. While the risk of islanding is low even in these cases, it is often difficult to deal with these scenarios in a simplified interconnection screening process. This type of analysis could provide a basis to establish a practical anti- islanding screening methodology for these complex scenarios, with the goal of reducing the number of required detailed studies. Eight generic Groups of islanding detection behavior are defined, and examples of each are used in the simulations. The results indicate that islanding detection methods lose effectiveness at significantly different rates as the composition of the distributed energy resources (DERs) varies, with some methods remaining highly effective over a wide range of conditions.

More Details

Small commercial inverter laboratory evaluations of UL 1741 SA grid-support function response times

2017 IEEE 44th Photovoltaic Specialist Conference, PVSC 2017

Gonzalez, Sigifredo; Johnson, Jay; Reno, Matthew J.; Zgonena, Timothy

Photovoltaic (PV) distributed energy resources (DER) have reached approximately 27 GW in the U.S., and the solar penetration rate continues to increase. This growth is expected to continue, causing challenges for grid operators who must maintain grid stability, reliability, and resiliency. To minimize adverse effects on the performance of electrical power system (EPS) with increasing levels of variable renewable generation, photovoltaic inverters must implement grid-support capabilities, allowing the DER to actively participate in grid support operations and remain connected during short-term voltage and frequency anomalies. These functions include voltage and frequency regulation features that adjust DER active and reactive power at the point of common coupling. To evaluate the risk of these functions conflicting with traditional distribution system voltage regulation equipment, researchers used several methods to quantify EPS-support function response times for autonomous voltage regulation functions (volt-var function). Based on this study, no adverse interactions between PV inverters with volt-var functions and load tap changing transformers or capacitor banks were discovered.

More Details

Small commercial inverter laboratory evaluations of UL 1741 SA grid-support function response times

2017 IEEE 44th Photovoltaic Specialist Conference, PVSC 2017

Gonzalez, Sigifredo; Johnson, Jay; Reno, Matthew J.; Zgonena, Timothy

Photovoltaic (PV) distributed energy resources (DER) have reached approximately 27 GW in the U.S., and the solar penetration rate continues to increase. This growth is expected to continue, causing challenges for grid operators who must maintain grid stability, reliability, and resiliency. To minimize adverse effects on the performance of electrical power system (EPS) with increasing levels of variable renewable generation, photovoltaic inverters must implement grid-support capabilities, allowing the DER to actively participate in grid support operations and remain connected during short-term voltage and frequency anomalies. These functions include voltage and frequency regulation features that adjust DER active and reactive power at the point of common coupling. To evaluate the risk of these functions conflicting with traditional distribution system voltage regulation equipment, researchers used several methods to quantify EPS-support function response times for autonomous voltage regulation functions (volt-var function). Based on this study, no adverse interactions between PV inverters with volt-var functions and load tap changing transformers or capacitor banks were discovered.

More Details

PV Systems Reliability Final Technical Report

Lavrova, Olga; Flicker, Jack D.; Johnson, Jay; Armijo, Kenneth M.; Gonzalez, Sigifredo; Schindelholz, Eric; Sorensen, Neil R.; Yang, Benjamin B.

The continued exponential growth of photovoltaic technologies paves a path to a solar-powered world, but requires continued progress toward low-cost, high-reliability, high-performance photovoltaic (PV) systems. High reliability is an essential element in achieving low-cost solar electricity by reducing operation and maintenance (O&M) costs and extending system lifetime and availability, but these attributes are difficult to verify at the time of installation. Utilities, financiers, homeowners, and planners are demanding this information in order to evaluate their financial risk as a prerequisite to large investments. Reliability research and development (R&D) is needed to build market confidence by improving product reliability and by improving predictions of system availability, O&M cost, and lifetime. This project is focused on understanding, predicting, and improving the reliability of PV systems. The two areas being pursued include PV arc-fault and ground fault issues, and inverter reliability.

More Details

Final Technical Report: Characterizing Emerging Technologies

King, Bruce H.; Hansen, Clifford; Stein, Joshua; Riley, Daniel; Gonzalez, Sigifredo

The Characterizing Emerging Technologies project focuses on developing, improving and validating characterization methods for PV modules, inverters and embedded power electronics. Characterization methods and associated analysis techniques are at the heart of technology assessments and accurate component and system modeling. Outputs of the project include measurement and analysis procedures that industry can use to accurately model performance of PV system components, in order to better distinguish and understand the performance differences between competing products (module and inverters) and new component designs and technologies (e.g., new PV cell designs, inverter topologies, etc.).

More Details

Optimization of a Virtual Power Plant to Provide Frequency Support

Neely, Jason C.; Johnson, Jay; Gonzalez, Sigifredo; Lave, Matt; Delhotal, Jarod J.

Increasing the penetration of distributed renewable sources, including photovoltaic (PV) sources, poses technical challenges for grid management. The grid has been optimized over decades to rely upon large centralized power plants with well-established feedback controls, but now non-dispatchable, renewable sources are displacing these controllable generators. This one-year study was funded by the Department of Energy (DOE) SunShot program and is intended to better utilize those variable resources by providing electric utilities with the tools to implement frequency regulation and primary frequency reserves using aggregated renewable resources, known as a virtual power plant. The goal is to eventually enable the integration of 100s of Gigawatts into US power systems.

More Details

Accelerating Development of Advanced Inverters

Neely, Jason C.; Johnson, Jay; Gonzalez, Sigifredo; Ropp, Michael

Increasing the penetration of distributed renewable sources, including photovoltaic (PV) generators, poses technical challenges for grid management. The grid has been optimized over decades to rely on large centralized power plants with well-established feedback controls. Conventional generators provide relatively constant dispatchable power and help to regulate both voltage and frequency. In contrast, photovoltaic (PV) power is variable, is only as predictable as the weather, and provides no control action. Thus, as conventional generation is displaced by PV power, utility operation stake holders are concerned about managing fluctuations in grid voltage and frequency. Furthermore, since the operation of these distributed resources are bound by certain rules that require they stop delivering power when measured voltage or frequency deviate from the nominal operating point, there are also concerns that a single grid event may cause a large fraction of generation to turn off, triggering a black out or break-up of an electric power system.

More Details

Performance Test Protocol for Evaluating Inverters Used in Grid-Connected Photovoltaic Systems

Gonzalez, Sigifredo; Newmiller, Jeff; Blodgett, Douglas

Interconnection equipment that connects distributed resources (DR) to an electrical power system (EPS) are expected to do so efficiently. Standardized test procedures are necessary to establish methods for verifying inverter performance that leads to comparable results. These test procedures are provided as a repeatable, independent means of measuring inverter performance regarding maximum continuous power rating, conversion efficiency, and tare loss characteristics.

More Details