Publications

Results 51–75 of 86
Skip to search filters

Response of Nuclear Power Plant Instrumentation Cables Exposed to Fire Conditions

Muna, Alice B.; LaFleur, Chris B.; Brooks, Dusty M.

This report presents the results of instrumentation cable tests sponsored by the US Nuclear Regulatory Commission (NRC) Office of Nuclear Regulatory Research and performed at Sandia National Laboratories (SNL). The goal of the tests was to assess thermal and electrical response behavior under fire-exposure conditions for instrumentation cables and circuits. The test objective was to assess how severe radiant heating conditions surrounding an instrumentation cable affect current or voltage signals in an instrumentation circuit. A total of thirty-nine small-scale tests were conducted. Ten different instrumentation cables were tested, ranging from one conductor to eight-twisted pairs. Because the focus of the tests was thermoset (TS) cables, only two of the ten cables had thermoplastic (TP) insulation and jacket material and the remaining eight cables were one of three different TS insulation and jacket material. Two instrumentation cables from previous cable fire testing were included, one TS and one TP. Three test circuits were used to simulate instrumentation circuits present in nuclear power plants: a 4–20 mA current loop, a 10–50 mA current loop and a 1–5 VDC voltage loop. A regression analysis was conducted to determine key variables affecting signal leakage time.

More Details

Application of quantitative risk assessment for performance-based permitting of hydrogen fueling stations

International Journal of Hydrogen Energy

LaFleur, A.C.; Muna, Alice B.; Groth, K.M.

NFPA 2, Hydrogen Technologies Code, allows the use of risk-informed approaches to permitting hydrogen fueling installations, through the use of performance-based evaluations of specific hydrogen hazards. However, the hydrogen fueling industry in the United States has been reluctant to implement the performance-based option because the perception is that the required effort is cost prohibitive and there is no guarantee that the Authority Having Jurisdiction (AHJ) would accept the results. This report provides a methodology for implementing a performance-based design of an outdoor hydrogen refueling station that does not comply with specific prescriptive separation distances. Performance-based designs are a code-compliant alternative to meeting prescriptive requirements. Compliance is demonstrated by evaluating a compliant prescriptive-based refueling station design with a performance-based design approach using Quantitative Risk Assessment (QRA) methods and hydrogen risk tools. This template utilizes the Sandia-developed QRA tool, Hydrogen Risk Analysis Model (HyRAM), to calculate risk values when developing risk-equivalent designs. HyRAM combines reduced-order deterministic models that characterize hydrogen release and flame behavior with probabilistic risk models to quantify risk values. Each project is unique and this template is not intended to cover unique, site-specific characteristics. Instead, example content and a methodology are provided for a representative hydrogen refueling site which can be built upon for new hydrogen applications.

More Details

Instrumentation Cables Test Plan

Muna, Alice B.; LaFleur, Chris B.

The objective of this research is to better understand the fire-induced failure modes of instrumentation cables and evaluate the potential effect those failure modes could have on plant instrumentation circuits (i.e., circuit, component, and/or system response). In particular, this research is intended to better quantify the signal leakage that may occur before catastrophic failure in instrumentation circuits.

More Details

Failure analysis of LNG rail locomotives

2017 Joint Rail Conference, JRC 2017

LaFleur, Chris B.; Muna, Alice B.; Groth, Katrina G.; St Pierre, Matthew; Shurland, Melissa

This paper presents a risk assessment of a Liquefied Natural Gas (LNG)/diesel hybrid locomotive to identify and rank failures that could result in the release of LNG or Gaseous Natural Gas (GNG) to the surrounding environment. The Federal Railroad Administration (FRA) will analyze industry safety assessments of the proposed rail vehicles and the goal of this risk analysis is to identify and prioritize hazard scenarios so the FRA can ensure that they are properly addressed. For operational activities, a Failure Modes and Effects Analysis (FMEA) was performed to identify high risk failure modes. A modified hazard and operability study (HAZOP) methodology was used to analyze hazard scenarios for the maintenance activities for the LNG and Compressed Natural Gas (CNG) dual-fuel locomotives and the LNG tender car. Because refueling operations are highly dependent on human interactions, a human factors assessment was also performed on a sample refueling procedure to identify areas of improvement and identify best practices for analyzing future procedures. The FMEA resulted in the identification of 87 total failure modes for the operational phase, three of which were deemed to have a High risk priority, all involving the cryogenic storage tank. The HAZOP for the LNG tender resulted in the identification of eight credible hazard scenarios and the HAZOP for the locomotive in the maintenance mode identified 27 credible hazard scenarios. The high and medium risk failure modes and hazard scenarios should be prioritized for further analysis.

More Details

Instrumentation Cables Test Plan

Muna, Alice B.; LaFleur, Chris B.

A fire at a nuclear power plant (NPP) has the potential to damage structures, systems, and components important to safety, if not promptly detected and suppressed. At Browns Ferry Nuclear Power Plant on March 22, 1975, a fire in the reactor building damaged electrical power and control systems. Damage to instrumentation cables impeded the function of both normal and standby reactor coolant systems, and degraded the operators’ plant monitoring capability. This event resulted in additional NRC involvement with utilities to ensure that NPPs are properly protected from fire as intended by the NRC principle design criteria (i.e., general design criteria 3, Fire Protection). Current guidance and methods for both deterministic and performance based approaches typically make conservative (bounding) assumptions regarding the fire-induced failure modes of instrumentation cables and those failure modes effects on component and system response. Numerous fire testing programs have been conducted in the past to evaluate the failure modes and effects of electrical cables exposed to severe thermal conditions. However, that testing has primarily focused on control circuits with only a limited number of tests performed on instrumentation circuits. In 2001, the Nuclear Energy Institute (NEI) and the Electric Power Research Institute (EPRI) conducted a series of cable fire tests designed to address specific aspects of the cable failure and circuit fault issues of concern1. The NRC was invited to observe and participate in that program. The NRC sponsored Sandia National Laboratories to support this participation, whom among other things, added a 4-20 mA instrumentation circuit and instrumentation cabling to six of the tests. Although limited, one insight drawn from those instrumentation circuits tests was that the failure characteristics appeared to depend on the cable insulation material. The results showed that for thermoset insulated cables, the instrument reading tended to drift and fluctuate, while the thermoplastic insulated cables, the instrument reading fell off-scale rapidly. From an operational point of view, the latter failure characteristics would likely be identified as a failure from the effects of fire, while the former may result in inaccurate readings.

More Details
Results 51–75 of 86