Early-Time (E1) High-Altitude Electromagnetic Pulse Effects on Trip Coils

Sanabria, David E.; Bowman, Tyler B.; Guttromson, Ross G.; Halligan, Matthew H.; Le, Ken L.; Lehr, J.M.

A High-Altitude Electromagnetic Pulse (HEMP) is a potential threat to the power grid. HEMP can couple to transmission lines and cables, causing significant overvoltages which can be harmful to line connected equipment. The effects of overvoltages on various types of power systems components need to be understood. HEMP effects on trip coils were tested and presented in this report. A high voltage pulser was built to replicate the induced voltage waveform from a HEMP. The pulser was used to test breaker trip coils with increasing pulse magnitudes ranging from 20 kV to 80 kV. The State-of-Health of each trip coils was measured via mechanical operation and impedance measurements before and after each insult to identify any damage or degradation to the trip coils. Dielectric breakdown was observed at the conductor leads during testing, causing the HEMP insult to be diverted to the grounded casing. However, the dielectric breakdown did not cause interference with regular device operation.

More Details

Early-Time (E1) High-Altitude Electromagnetic Pulse Effects on Transient Voltage Surge Suppressors

Llanes, Rodrigo E.; Halligan, Matthew H.; Guttromson, Ross G.; Lehr, J.M.; dougan, nikita d.; Le, Ken L.; diaz, david d.

Determining the effectiveness of surge and pulse protection devices in the United States power grid against effects of a High-Altitude Electromagnetic Pulse (HEMP) is crucial in determining the present state of grid resilience. Transient Voltage Surge Suppressors (TVSS) are used to protect loads in substations from transient overvoltages. Designed to mitigate the effects of lightning, their response to a HEMP event is unknown and was determined. TVSSs were tested in two unique configurations using a pulser that generates pulses in the tens of nanoseconds scale to determine their protective capability as well as to determine their self-resilience against HEMP pulses. Testing concluded that TVSS devices adequately protect against microsecond scale pulses like lightning but do not protect against pulses resembling HEMP events. It suggests that TVSS devices should not be relied upon to mitigate the effects of HEMP pulses.

More Details

Impact of time-varying loads on the programmable pulsed power driver called genesis

Digest of Technical Papers-IEEE International Pulsed Power Conference

Glover, Steven F.; Davis, Jean-Paul D.; Schneider, Larry X.; Reed, Kim W.; Pena, Gary P.; Hall, Clint A.; Hanshaw, Heath L.; Hickman, Randy J.; Hodge, K.C.; Lemke, Raymond W.; Lehr, J.M.; Lucero, D.J.; McDaniel, Dillon H.; Puissant, J.G.; Rudys, Joseph M.; Sceiford, Matthew S.; Tullar, S.J.; Van De Valde, D.M.; White, F.E.; Warne, Larry K.; Coats, Rebecca S.; Johnson, William Arthur.

The success of dynamic materials properties research at Sandia National Laboratories has led to research into ultra-low impedance, compact pulsed power systems capable of multi-MA shaped current pulses with rise times ranging from 220-500 ns. The Genesis design consists of two hundred and forty 200 kV, 80 kA modules connected in parallel to a solid dielectric disk transmission line and is capable of producing 280 kbar of magnetic pressure (>500 kbar pressure in high Z materials) in a 1.75 nH, 20 mm wide stripline load. Stripline loads operating under these conditions expand during the experiment resulting in a time-varying load that can impact the performance and lifetime of the system. This paper provides analysis of time-varying stripline loads and the impact of these loads on system performance. Further, an approach to reduce dielectric stress levels through active damping is presented as a means to increase system reliability and lifetime. © 2011 IEEE.

More Details

Status of genesis a 5 MA programmable pulsed power driver

Digest of Technical Papers-IEEE International Pulsed Power Conference

Glover, Steven F.; White, F.E.; Foster, P.J.; Lucero, D.J.; Schneider, Larry X.; Reed, Kim W.; Pena, Gary P.; Davis, Jean-Paul D.; Hall, Clint A.; Hickman, Randy J.; Hodge, K.C.; Lemke, Raymond W.; Lehr, J.M.; McDaniel, Dillon H.; Puissant, J.G.; Rudys, Joseph M.; Sceiford, Matthew S.; Tullar, S.J.; Van De Valde, D.M.

Genesis is a compact pulsed power platform designed by Sandia National Laboratories to generate precision shaped multi-MA current waves with a rise time of 200-500 ns. In this system, two hundred and forty, 200 kV, 80 kA modules are selectively triggered to produce 280 kbar of magnetic pressure (>500 kbar pressure in high Z materials) in a stripline load for dynamic materials properties research. This new capability incorporates the use of solid dielectrics to reduce system inductance and size, programmable current shaping, and gas switches that must perform over a large range of operating conditions. Research has continued on this technology base with a focus on demonstrating the integrated performance of key concepts into a Genesis-like prototype called Protogen. Protogen measures approximately 1.4 m by 1.4 m and is designed to hold twelve Genesis modules. A fixed inductance load will allow rep-rate operation for component reliability and system lifetime experiments at the extreme electric field operating conditions expected in Genesis. © 2011 IEEE.

More Details

Surface interactions involved in flashover with high density electronegative gases

Warne, Larry K.; Jorgenson, Roy E.; Lehr, J.M.

This report examines the interactions involved with flashover along a surface in high density electronegative gases. The focus is on fast ionization processes rather than the later time ionic drift or thermalization of the discharge. A kinetic simulation of the gas and surface is used to examine electron multiplication and includes gas collision, excitation and ionization, and attachment processes, gas photoionization and surface photoemission processes, as well as surface attachment. These rates are then used in a 1.5D fluid ionization wave (streamer) model to study streamer propagation with and without the surface in air and in SF6. The 1.5D model therefore includes rates for all these processes. To get a better estimate for the behavior of the radius we have studied radial expansion of the streamer in air and in SF6. The focus of the modeling is on voltage and field level changes (with and without a surface) rather than secondary effects, such as, velocities or changes in discharge path. An experiment has been set up to carry out measurements of threshold voltages, streamer velocities, and other discharge characteristics. This setup includes both electrical and photographic diagnostics (streak and framing cameras). We have observed little change in critical field levels (where avalanche multiplication sets in) in the gas alone versus with the surface. Comparisons between model calculations and experimental measurements are in agreement with this. We have examined streamer sustaining fields (field which maintains ionization wave propagation) in the gas and on the surface. Agreement of the gas levels with available literature is good and agreement between experiment and calculation is good also. Model calculations do not indicate much difference between the gas alone versus the surface levels. Experiments have identified differences in velocity between streamers on the surface and in the gas alone (the surface values being larger).

More Details

Streamer initiation in volume and surface discharges in atmospheric gases

Proceedings of the 2008 IEEE International Power Modulators and High Voltage Conference, PMHVC

Lehr, J.M.; Warne, Larry K.; Jorgenson, Roy E.; Wallace, Z.R.; Hodge, K.C.; Caldwell, Michele C.

It is generally acknowledged that once a highly conductive channel is established between two charged and conducting materials, electrical breakdown is well established and difficult to interrupt. An understanding of the initiation mechanism for electrical breakdown is crucial for devising mitigating methods to avoid catastrophic failures. Both volumetric and surface discharges are of interest. An effort is underway where experiments and theory are being simultaneously developed. The experiment consists of an impedance matched discharge chamber capable of investigating various gases and pressures to ten atmospheres. In addition to current and voltage measurements, a high dynamic range streak camera records streamer velocities. The streamer velocities are particularly valuable for comparison with theory. A streamer model is being developed which includes photo-ionization and particle interactions with an insulating surface. The combined theoretical and experimental effort is aimed at detailed comparisons of streamer development as well as a quantitative understanding of how streamers interact with dielectric surfaces and the resulting effects on breakdown voltage. © 2008 IEEE.

More Details

A 5-megavolt, 600-kiloampere laser-triggered gas switch for use on Z-R: Comparison of experiments and simulations

Digest of Technical Papers-IEEE International Pulsed Power Conference

Woodworth, Joseph R.; Rosenthal, Stephen E.; Lehr, J.M.; Maenchen, John E.; Elizondo, J.; Johnson, D.L.; Corley, J.P.; Hodge, K.C.; Drennan, S.A.; Guthrie, D.W.

The Z Refurbishment project is designed to increase the peak current to the load on Z to ∼26 MA in a 100-ns wide power pulse. This current is achieved by summing the current from 36 independent pulse-power modules. To meet these requirements, we have designed and constructed an SF6-insulated gas switch that can hold off 5.5 MV and conduct a peak current of 600 kA for over a hundred shots. The gas switch is charged by a Marx generator in ∼1 microsecond and transfers about 200-kilojoules of energy and 0.25 Coulombs of charge to a pulse-forming line in a ∼150-ns-wide power pulse peaking at 2.5 TW. The gas switch oonsists of a laser-triggered section holding off 15% of the voltage followed by 25 self-breakdown gaps. The self-breaking gaps are designed to provide multiple breakdown arcs in order to lower the overall inductance of the switch. The gas switch is submerged in transformer oil during operation. In this work, we show how simulation and experiment have worked together, first to verify proper operation of the switch, and then to solve problems with the switch design that arose during testing. © 2005 IEEE.

More Details

Performance of self-closing diverter switches for ZR/Z20 marx and intermediate store protection

Digest of Technical Papers-IEEE International Pulsed Power Conference

Douglas, J.; Banister, J.; Corcoran, P.; Goyer, J.; Miller, R.; Morton, D.; Nishimoto, H.; Smith, I.; Corley, J.; Drennan, S.; Guthrie, D.; Hodge, K.; Lehr, J.M.; Maenchen, John E.; Smith, D.; Sears, R.

The ZR refurbishment project [1] at Sandia National Laboratories (SNL) required a set of diverter switches to protect the Marx generators and intermediate storage (IS) capacitors from Marx pre-fire and/or laser triggered output switch (LTS) no-fire. Thirty-six such diverters, one for each Marx-IS set, will need to operate reliably over the full range of Marx charge voltages and LTS anticipated closure times. Operating voltage is up to 6 MV. A self-closing oil switch diverter was selected and design work began in late 2002. The first diverter (Phase I or just P1) was delivered in the summer of 2003 and tested on SNL's Z20 test-bed. Based on test results, operational experience and overall project budgetary concerns, it was decided to re-design the diverter, resulting a simpler, less costly switch. This new self-closing oil switch (Phase II or P2) was fielded at SNL on the Z20 test-bed in late 2004. Both designs include adjustable electrodes to control the closure time. Also incorporated is a mechanical clamp that minimizes or shorts the oil gap until Marx charge is complete. Both diverters feature liquid resistors sized to safely absorb the energy stored in the Marx or IS. This paper describes the design and test results from these diverters. © 2005 IEEE.

More Details