Publications

Publications / SAND Report

Validation predictions of a 13 m/s cross-wind fire for Fuego and the University of Waterloo dataset

Gill, Walt; Evans, Gregory H.

Detailed herein are the results of a validation comparison. The experiment involved a 2 meter diameter liquid pool of Jet-A fuel in a 13 m/s crosswind. The scenario included a large cylindrical blocking object just down-stream of the fire. It also included seven smaller calorimeters and extensive instrumentation. The experiments were simulated with Fuego. The model included several conduction regions to model the response of the calorimeters, the floor, and the large cylindrical blocking object. A blind comparison was used to compare the simulation predictions with the experimental data. The more upstream data compared very well with the simulation predictions. The more downstream data did not compare very well with the simulation predictions. Further investigation suggests that features omitted from the original model contributed to the discrepancies. Observations are made with respect to the scenario that are aimed at helping an analyst approach a comparable problem in a way that may help improve the potential for quantitative accuracy.