Small commercial inverter laboratory evaluations of UL 1741 SA grid-support function response times
Gonzalez, Sigifredo G.; Johnson, Jay; Reno, Matthew J.; Zgonena, Timothy
Photovoltaic (PV) distributed energy resources (DER) have reached approximately 27 GW in the U.S., and the solar penetration rate continues to increase. This growth is expected to continue, causing challenges for grid operators who must maintain grid stability, reliability, and resiliency. To minimize adverse effects on the performance of electrical power system (EPS) with increasing levels of variable renewable generation, photovoltaic inverters must implement grid-support capabilities, allowing the DER to actively participate in grid support operations and remain connected during short-term voltage and frequency anomalies. These functions include voltage and frequency regulation features that adjust DER active and reactive power at the point of common coupling. To evaluate the risk of these functions conflicting with traditional distribution system voltage regulation equipment, researchers used several methods to quantify EPS-support function response times for autonomous voltage regulation functions (volt-var function). Based on this study, no adverse interactions between PV inverters with volt-var functions and load tap changing transformers or capacitor banks were discovered.