Publications
Identifying errors in service transformer connections
Blakely, Logan; Reno, Matthew J.
Distribution system models play a critical role in the modern grid, driving distributed energy resource integration through hosting capacity analysis and providing insight into critical areas of interest such as grid resilience and stability. Thus, the ability to validate and improve existing distribution system models is also critical. This work presents a method for identifying service transformers which contain errors in specifying the customers connected to the low-voltage side of that transformer. Pairwise correlation coefficients of the smart meter voltage time series are used to detect when a customer is not in the transformer grouping that is specified in the model. The proposed method is demonstrated both on synthetic data as well as a real utility feeder, and it successfully identifies errors in the transformer labeling in both datasets.