Distribution Feeder Fault Comparison Utilizing a Real-Time Power Hardware-in-the-Loop Approach for Photovoltaic System Applications

Darbali-Zamora, Rachid; Hernandez Alvidrez, Javier H.; Summers, Adam; Gurule, Nicholas S.; Reno, Matthew J.; Johnson, Jay B.

Power outages are a challenge that utility companies must face, with the potential to affect millions of customers and cost billions in damage. For this reason, there is a need for developing approaches that help understand the effects of fault conditions on the power grid. In distribution circuits with high renewable penetrations, the fault currents from DER equipment can impact coordinated protection scheme implementations so it is critical to accurately analyze fault contributions from DER systems. To do this, MATLAB/Simulink/RT-Labs was used to simulate the reduced-order distribution system and three different faults are applied at three different bus locations in the distribution system. The use of Real-Time (RT) Power Hardware-in-the-Loop (PHIL) simulations was also used to further improve the fidelity of the model. A comparison between OpenDSS simulation results and the Opal-RT experimental fault currents was conducted to determine the steady-state and dynamic accuracy of each method as well as the response of using simulated and hardware PV inverters. It was found that all methods were closely correlated in steady-state, but the transient response of the inverter was difficult to capture with a PV model and the physical device behavior could not be represented completely without incorporating it through PHIL.